Operating Instruction
21
Picture 11 Picture 12
12
Picture 13 Picture 14
Mounting the wallmounted kit on the Technovar
BEFORE REMOVING THE FREQUENCY INVERTER COVER THE SYSTEM MUST BE DIS-CONNECTED
FROM THE POWER SUPPLY. AFTER SWITCHING OFF THE POWER SUPPLY WAIT AT LEAST 5
MINUTES BEFORE STARTING WORK ON OR IN THE TECHNOVAR DRIVE HEAD.
Mounting the fan-board
Loosen the 4 main screws from the Technovar cover and also the 8 screws holding the
control-card.
Then remove the Technovar cover carefully. (Take care with the control-card and the GND-
Cable.)
Picture 3 shows you the fan-board (incl. the 3 fuses 1A/500V- picture 3/G) that you can fix
with the 3 plastic-distances in the 3 holes which are made for. (Picture 4)
The power supply for the fan-board comes from the connections L1, L2, L3 on the primary-
side from the rectifier-board.
Please fasten the connection screw as well and connect the right cable with the right
connection
Compare the cable number and the connection number. (Picture 5).
Connecting the control-cable